>> P.99
OthersPowerlineSPDSignallineSPDSPDforLANandcoaxialOthersMetalOxideVaristorHighVoltageArresterCheckerAT-HSeries,AT-H80K-,AT-H100K-AT-H40K-,AT-H50K-,AT-H60K-Measuresoperationreferencevoltageofsurgearrestersupto100kVDCFeatures1.Capableofmeasuringoperatingreferencevoltagesupto40to100kVDC2.Easytooperate3.Equippedwithovervoltageandovercurrenterrordetectionfunctions4.BuzzeralertstheuserduringmeasurementTypeAT-HK-1:SupplyvoltageAC100-120V2:SupplyvoltageAC200-240V40:MaximumoutputvoltageDC40kV50:MaximumoutputvoltageDC50kV60:MaximumoutputvoltageDC60kV80:MaximumoutputvoltageDC80kV100:MaximumoutputvoltageDC100kVAccessoriesACpowercable(2.5m)×1pieceMeasurementcableofvoltageside(2.5m)×1pieceGroundwire(2m)×1pieceGroundrod×1pieceCalibrationServicesCalibrationserviceisavailableforthisproduct.Periodiccalibrationofthisproductisrecommended.SpecificationTypePowerSourcePowerconsumptionMaximumoutputvoltageOutputAccuracyOutputpolarityMeasurementMeasurementrangeEvaluationofanabnormalityEnvironmentalconditionMassAT-H40K-AT-H50K-AT-H60K-AT-H80K-AT-H100K-DC40kVDC50kVAT-HAT-HK-1:AC100-120V(50/60Hz)K-2:AC200-240V(50/60Hz)250WorlessDC60kVVoltage:Within±2%F.S.Current:Within±30μAPositiveDCreferencevoltage(DCV1mA)5to95%ofmaximumoutputvoltageDC80kVDC100kVOvervoltageerror:When95%ofthemaximumoutputvoltageisreachedOvercurrenterror:Whenoutputvoltageislessthan1kVandcurrentowsmorethan0.7mATemperature:0°Cto+50°CHumidity:0to80%(nocondensation)About20kgAbout35kgOptionalgoodsIndicatorlight(AT-PL-2,red,connectioncable2m)HighVoltageArresterCheckerAT-HSeries|AT-H40K-,AT-H50K-,AT-H60K-,AT-H80K-,AT-H100K-99